Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T21CM03103
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/21/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | The submitted ventilation calculations are incomplete and incorrect; see Section 403.3.1.1.2.3, IMC 2018 for the calculations required The kitchen also requires 0.7 CFM of exhaust per square foot (Table 403.3.1.1, IMC 2018). The lack of a return in the planning room and in the utility room will result in portions of the egress elements functioning as ducts (Section 601.2, IMC 2018). [Initial comment: Show how the mechanical system serving the new planning and office spaces has been modified to provide adequate ventilation for both rooms. Reference: Section 401.2, IMC 2018.] |
| 06/24/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |