Permit Number: T21CM03103
Parcel: 107083250

Address:
701 W TIPTON DR

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM03103
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/21/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change The submitted ventilation calculations are incomplete and incorrect; see Section 403.3.1.1.2.3, IMC 2018 for the calculations required The kitchen also requires 0.7 CFM of exhaust per square foot (Table 403.3.1.1, IMC 2018). The lack of a return in the planning room and in the utility room will result in portions of the egress elements functioning as ducts (Section 601.2, IMC 2018). [Initial comment: Show how the mechanical system serving the new planning and office spaces has been modified to provide adequate ventilation for both rooms. Reference: Section 401.2, IMC 2018.]
06/24/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved