Permit Number: T21CM03103
Parcel: 107083250

Address:
701 W TIPTON DR

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM03103
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/14/2021 JPEELDA1 FIRE REVIEW Approved
04/15/2021 ROBERT SHERRY WATER REVIEW Completed
04/19/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
04/19/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Show how the mechanical system serving the new planning and office spaces has been modified to provide adequate ventilation for both rooms. Reference: Section 401.2, IMC 2018.
04/28/2021 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/28/2021 PCAMARE1 ENGINEERING REVIEW Passed
04/28/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/06/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.

Provide detailed descriptions of electrical devices, luminaires, branch circuit and panel designation.

Provide for tamper resistant receptacles as required per NEC art 406.12.

What controls the ceiling fan?



Ref; 2018 IBC sec 107.2.1, 2017 NEC, City of Tucson Commercial Permit/Plan Submittal Requirements.
05/10/2021 STEVE SHIELDS ZONING REVIEW Approved