Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM03103
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/14/2021 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 04/15/2021 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 04/19/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 04/19/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Show how the mechanical system serving the new planning and office spaces has been modified to provide adequate ventilation for both rooms. Reference: Section 401.2, IMC 2018. |
| 04/28/2021 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 04/28/2021 | PCAMARE1 | ENGINEERING | REVIEW | Passed | |
| 04/28/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 05/06/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. Provide detailed descriptions of electrical devices, luminaires, branch circuit and panel designation. Provide for tamper resistant receptacles as required per NEC art 406.12. What controls the ceiling fan? Ref; 2018 IBC sec 107.2.1, 2017 NEC, City of Tucson Commercial Permit/Plan Submittal Requirements. |
| 05/10/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved |