Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T21CM03016
Parcel: Unknown

Address:
3550 E CORONA RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM03016
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/15/2021 JPEELDA1 FIRE REVIEW Approved
04/26/2021 CTREVIL1 ZONING REVIEW Passed
04/26/2021 CTREVIL1 ENGINEERING REVIEW Passed
04/27/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM03016

GENERAL:
o Provide written responses to all review comments.
o Provide a complete plan set.
o Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
APPROVED

BUILDING REVIEW COMMENTS:
Denied
1. Phase 2 Sheet 13, Ship Ladder Assembly: The treads and risers of the ship ladder do not the meet the minimum
requirements of 1011.15.2
2. Phase 2 Sheet 13, Ship Ladder Assembly: It appears that distance between the handrails do not comply with Section
1011.15
3. All platforms that are 30" above the ground is required to have guards in compliance with Section 1015. It appears that are
some platform that will not have guards in some places. Provide clarification for the areas of the platforms marked with an
asterisk.
4. Phase 1 Sheet 14, Ship Ladder Assembly: The treads and risers of the ship ladder do not the meet the minimum
requirements of 1011.15.2
5. Phase 1 Sheet 14, Ship Ladder Assembly: It appears that distance between the handrails do not comply with Section
1011.15
6. Provide a detailed code analysis of the project that includes occupancy classification, construction types and occupancy
load calculations. Also, include a list of the new platforms that include square footage of each.
Electrical Review
DENIED
1 00124-001001 TITLE PAGE: Set needs a cable schedule to identify feeders to the wire size/ratings for the
conductors feeding into and out of the 1000 amp Main Distribution Panel and sub feeder circuit breakers. Cannot determine
if the Circuit Breakers protect the cables/conductors as they are not identified.
Need to also provide information on grounding for all of the major panels.
19 00124-101301 CDP01 THREE LINES: Cannot determine if feeders for 1000-amp Main Disconnect are
acceptable. Need to call out conductors and raceway.
20 00124-001201 CP01 SINGLE LINES: No Electrical issues. Settings on CBs seem optimistically accurate.
Most CB selections do not have the stated resolution.
MECHANICAL REVIEW COMMENTS:
NA

PLUMBING REVIEW COMMENTS:
NA