Permit Number: T21CM03003
Parcel: 135061910

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T21CM03003
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/22/2021 JGARCIA1 ZONING REVIEW Reqs Change FROM: PDSD Zoning Review
PROJECT: T21CM03003
2125 S Avenida Planeta
Addition – Garage, Laundry, Bath & Workshop (Revision 1)

TRANSMITTAL DATE: December 2, 2021

This site is located in the R-1 zone (UDC 4.7.8). A single-family residence is permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.B.5 - .9.

1. The proposed revision outlined changes to mechanical, electrical and plumbing systems. However, the layout of the addition as it relates to the property appears to have changed. This needs to be resolved.
2. The approved plans illustrate a setback on the south property line of 8'8". The Revision illustrates a proposed setback of 4'6" and 5'8". Based on a wall height of 10'8" the minimum required setback is 7'2".
3. A redesign to meet minimum setbacks or approval of a Design Development Option is required. See info on the DDO online here: https://www.tucsonaz.gov/files/pdsd/forms/DDO_for_Setback_and_Height_UDC_8.11.20.pdf. You may also contact Mark.Castro@tucsonaz.gov for more information.

-Elisa Hamblin, AICP
Site Review Section Manager
elisa.hamblin@tucsonaz.gov
12/02/2021 JGARCIA1 BUILDING-RESIDENTIAL REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
12/02/2021 NGARCIA3 OUT TO CUSTOMER Completed