Permit Number: T21CM02936
Parcel: 14041128B

Review Status: Completed

Review Details: OTHER

Permit Number - T21CM02936
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/28/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.

Provide plans and evidence on the plans that the proposed exterior lighting fully complies with the Outdoor Lighting Code. See section 104 for plan submittal requirements.

Provide lighting plans including a site plan with the following information on the plans;

(a) Provide a complete luminaire schedule for each parcel, if more that one, include for each separate parcel. Include shielding and lamp color output temperature.

(b) Size of the parcel in acres. It appears there are several parcels. If true, then provide total lumen calculations and all other required information for each parcel, per section 104.2.1.

(c)See table 401.1, lighting area and option and indicate this information in the lighting site plan for each parcel, also show the locations and types of all exterior luminaires including existing.

(d) Section 402.1 (light source color temperature requirements 3500K), shielding requirements, etc .

(e) Provide a complete inventory (quantities) for each type of luminaire on the parcel.

(f) Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2.

(g) Specify any exceptions used.

(h) Curfew lighting controls If applicable.

Do not confuse the Outdoor Lighting Code with the IECC.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2012 Tucson/Pima County Outdoor Lighting Code,

City of Tucson Commercial Plan Submittal Requirements
04/28/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. General: Please provide structural calculations for the light pole base design (Detail 1/E0.1).
05/03/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM02936
6803 S Palo Verde Rd
Site Lighting

TRANSMITTAL: May 3, 2021
This site is located in the I-1 zone (UDC 4.7.29). Commercial Storage is a permitted use in this zone (Table 4.8-5) subject to Use Specific Standards 4.9.10.A and 4.9.13.Q.

1. Development package DP21-0047 must be approved prior to these plans

If you have any questions about this transmittal, please contact Elisa Hamblin or Elisa.Hamblin@tucsonaz.gov.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/04/2021 IMONSHI1 OUT TO CUSTOMER Completed