Review Date Reviewer's Name Type of Review Description Status Comments
04/07/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Replacement of a Type I exhaust hood is new work and an Arizona Registrant is required to provide a mechanical design for the proposed hood replacement that clearly shows that the installation will comply with the requirements of Sections 302, 506, and 507, IMC 2018. Reference: Section 107.2.1, IBC 2018.