Permit Number: T21CM02868
Parcel: 12801013E

Review Status: Completed

Review Details: OTHER

Permit Number - T21CM02868
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/29/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. General: The Floor Plan must be prepared by a registered design professional per the IBC Section 107. Information on the drawing must include a code analysis, including square footage, occupancy classification, construction type, automatic sprinkler system requirements, and occupant load. In addition, plumbing fixture calculations must be indicated per the IBC Table 2902.1.
2. General: Is there any new construction indicated in this space, including new partitions, new openings, removed partitions, etc.? If so, please provide a project valuation (labor + materials)/
3. General: Is there an existing C of O for this space? If so, a new C of O may not be required at this time. Please contact our Records Department at Records@tucsonaz.gov or call
520-837-4899. If an existing C of O is found, please include that document in the next submittal.
4. General: Please provide written responses to all review comments.
05/03/2021 STEVE SHIELDS ZONING REVIEW Approved
05/11/2021 JPEELDA1 FIRE REVIEW Reqs Change 1. General: The Floor Plan must be prepared by a registered design professional per the IBC Section 107. Information on the drawing must include a code analysis, including square footage, occupancy classification, construction type, automatic sprinkler system requirements, and occupant load. In addition, plumbing fixture calculations must be indicated per the IBC Table 2902.1.
2. General: Is there any new construction indicated in this space, including new partitions, new openings, removed partitions, etc.? If so, please provide a project valuation (labor + materials)/
3. General: Is there an existing C of O for this space? If so, a new C of O may not be required at this time. Please contact our Records Department at Records@tucsonaz.gov or call
520-837-4899. If an existing C of O is found, please include that document in the next submittal.
4. General: Please provide written responses to all review comments.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/12/2021 IMONSHI1 OUT TO CUSTOMER Completed