Permit Number: T21CM02848
Parcel: 130083030

Address:
1720 S RICHEY BL

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T21CM02848
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/05/2021 SBLOOD1 ENGINEERING REVIEW Passed
04/19/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review


PROJECT:
T21CM02848
1720 S Richey Blv
Extend Existing Bedrooms

TRANSMITTAL: April 19, 2021
COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).

This site is located in the R-2 zone (UDC 4.7.9). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9.

Perimeter yard setbacks are based on a measurement from design grade to the highest point of the wall, see UDC Article 6.4.5.B.1 & Figure 6.4.5-A.

1. The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure’s wall facing each interior property line (Table 6.3-2.A). Based on a wall height of 11’-4” the required perimeter yard setbacks from the proposed extension to the north property line is 7’-7”, proposed setback is 4’-0”

2. Per Citation Park final plat the east & west property line dimension should be 55’, not 50’ as shown on the plan.

3. Include the shed shown on the plan in the lot coverage calculation.

The required DDO for the north perimeter yard setback is a separate submittal. DDO application and requirements can be found at: https://www.tucsonaz.gov/files/pdsd/forms/DDO_for_Setback_and_Height_UDC_8.11.20.pdf, and is submitted at: https://www.tucsonaz.gov/pdsd-filedrop, using the submission type “Zoning Administration”.
04/19/2021 SSHIELD1 NPPO REVIEW Passed
04/21/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change Provide a section detail of the truss and rafter interface. Show the ridge and slope of each roof side.

Show the location and size of gable attic vent.