Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T21CM02842
Parcel: 140420270

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM02842
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/14/2021 ROBERT SHERRY WATER REVIEW Completed
04/14/2021 JVINCEN1 FIRE REVIEW Approved
04/23/2021 LOREN MAKUS ENGINEERING REVIEW Passed
04/26/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/26/2021 STEVE SHIELDS ZONING REVIEW Approved
04/27/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM02842

GENERAL:
o Provide written responses to all review comments.
o Provide a complete plan set.
o Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
N/A

BUILDING REVIEW COMMENTS:
Denied
1. The occupancy classification listed is not correct. It's listed as a B occupancy. This occupancy most resembles an F-1 occupancy as it appears to manufacture optical goods. Correct and correlate with all other sheets.
2. As this is an F-1 occupancy a complete equipment layout is required that clearly shows a delineated egress paths.
3. Provide clarification on how this occupancy interacts with the rest of the building. The cover sheet states that it is nonseparated mixed use. Provide evidence that this tenant space complies with section 508.
4. This occupancy is required to be protected by a NFPA 13 sprinkler system per Section 903.2.4.
5. The breakroom occupant load is not calculated. Provide a proper occupant load calculation for the breakroom.
6. The floor plan indicate wall type tags. No wall types are provided. Provide wall types along with associated wall details.
7. Provide a separate demolition plan and new framing plan.

ELECTRICAL REVIEW COMMENTS
Approved

MECHANICAL REVIEW COMMENTS:
Denied
1. The sheet index does not list does not contain all of the mechanical sheets provided in the mechanical set. Multiple versions of the same sheet exist. Coordinate all drawings and resubmit.
2. The same details are on multiple pages. The mechanical set needs to be completely correlated and organized. 3. Provide a more detailed return air plenum that provides all appropriate details.
PLUMBING REVIEW COMMENTS:
APPROVED