Review Date Reviewer's Name Type of Review Description Status Comments
04/21/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.

Provide detailed information about the ā€˜U’ type luminaires shown on the module layout plans, including wiring methods, control, etc.. Provide 2012 Outdoor Lighting Code compliance.

Provide a grounding detail for the structural steel, racking and PV modules. NEC 690.43.

Please update the plans and re-submit.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, City of Tucson Commercial Permit/Plan Submittal Requirements.
04/23/2021 LOREN MAKUS ENGINEERING REVIEW Passed
04/26/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/27/2021 STEVE SHIELDS ZONING REVIEW Approved