Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM02831
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/21/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. Provide detailed information about the āUā type luminaires shown on the module layout plans, including wiring methods, control, etc.. Provide 2012 Outdoor Lighting Code compliance. Provide a grounding detail for the structural steel, racking and PV modules. NEC 690.43. Please update the plans and re-submit. Ref; 2018 IBC sec 107.2.1, 2017 NEC, City of Tucson Commercial Permit/Plan Submittal Requirements. |
| 04/23/2021 | LOREN MAKUS | ENGINEERING | REVIEW | Passed | |
| 04/26/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 04/27/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved |