Permit Number: T21CM02771
Parcel: 123060810

Address:
2022 E LEE ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T21CM02771
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/31/2021 PCAMARE1 ENGINEERING REVIEW Passed
04/16/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM02771
2022 E Lee St
Master Bedroom Addition.

TRANSMITTAL: April 16, 2021
COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).

This site is located in the R-1 zone (UDC 4.7.1). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9. 10.

1. The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure’s wall facing each interior property line (Table 6.3-2.A). Based on a wall height of 12’-10” the required perimeter yard setback to the west property line is 8’-7”, proposed setback is 3’-5”.

2. Provide a full floor plan for the entire house so that the number of bedrooms can be verified.
04/16/2021 SSHIELD1 NPPO REVIEW Passed
04/21/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change Provide a complete plan set for review after DDO approval.

A roof overhang extending into the 3 foot fire separation distance to property line requires one-hour fire rated materials applied to the underside of overhang.