Permit Number: T21CM02760
Parcel: 11611005K

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM02760
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/14/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.

The resubmitted plans were not designed to Commercial Electrical Plan Submittal standards. Provide complete electrical plans sealed by a Registrant registered in the State of Arizona.

Existing Site Electrical plans sealed by Dennis Coon EE in the year 2019 is considered a legal document and cannot be altered by the electrical contractor without the Registrant of records permission and the plans must be updated and re-sealed by this registrant. Provide complete power plans sealed and engineered by an Arizona Registrant that has knowledge in commercial electrical design to provide a complete code compliant electrical installation.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, City of Tucson Commercial Permit/Plan Submittal Requirements.