Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T21CM02760
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/26/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. Provide an electrical site plan showing the location of the existing meter, service equipment, disconnecting means, over current protection, AIC ratings and termination point of the new feeder, and another loads served by this feeder, receptacles, lighting etc. Provide a wiring detail showing the proposed wiring methods and local disconnecting means. Provide load calculations. Provide for a grounding electrode system at the shed. NEC 250.32. Ref; 2018 IBC sec 107.2.1, 2017 NEC, City of Tucson Commercial Permit/Plan Submittal Requirements. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/27/2021 | IMONSHI1 | OUT TO CUSTOMER | Completed |