Review Date Reviewer's Name Type of Review Description Status Comments
04/15/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide a more specific description of the polypropylene pipe (e.g. SDR, ASTM Standard). Reference: Section 1202.1, IMC 2018.
2. What is the minimum burial depth for the new pipe? Reference: Section 107.2.1, IBC 2018.
3. Show the location and dimensions of the required expansion loops. Reference: Section 1206.9, IMC 2018.
4. Provide underground facility tracer wires per ARS 40-360.22.