Permit Number: T21CM02719
Parcel: 14028019A

Address:
6220 S TUCSON BL

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T21CM02719
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/13/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet S2.7 (Plan View); Structural Calculations (Page 87): The steel beam on the Plan View indicates a W14x30, while the Structural Calculations indicate a W14x34. Please coordinate.
2. General: Please provide a Special Inspections Certificate with Parts A and B completed.
04/13/2021 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approv-Cond Canopy D beam section is indicated as a W14x34 in the calculations (Page 87), while the Plan View indicates a W14x30 beam. Please coordinate.
04/21/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
04/23/2021 LOREN MAKUS ENGINEERING REVIEW Passed
04/26/2021 STEVE SHIELDS ZONING REVIEW Reqs Change Until DP21-0046 has been approved Zoning cannot approve this plan.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/27/2021 IMONSHI1 OUT TO CUSTOMER Completed