Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/13/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet S2.7 (Plan View); Structural Calculations (Page 87): The steel beam on the Plan View indicates a W14x30, while the Structural Calculations indicate a W14x34. Please coordinate. 2. General: Please provide a Special Inspections Certificate with Parts A and B completed. |
04/13/2021 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Approv-Cond | Canopy D beam section is indicated as a W14x34 in the calculations (Page 87), while the Plan View indicates a W14x30 beam. Please coordinate. |
04/21/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
04/23/2021 | LOREN MAKUS | ENGINEERING | REVIEW | Passed | |
04/26/2021 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | Until DP21-0046 has been approved Zoning cannot approve this plan. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
04/27/2021 | IMONSHI1 | OUT TO CUSTOMER | Completed |