Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM02676
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/05/2021 | JVINCEN1 | FIRE | REVIEW | Approved | |
| 04/08/2021 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 04/19/2021 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T21CM02676 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: N/A BUILDING REVIEW COMMENTS: Denied 1. Provide a clearer site plan. The plan provided is not legible. Show dimensions to other buildings. 2. The lobby area would be considered an assembly area. This area provide queuing for the rest of the doctors office. Please adjust occupant load calculations and readjust. ELECTRICAL REVIEW COMMENTS Approved MECHANICAL REVIEW COMMENTS: Approved PLUMBING REVIEW COMMENTS: Approved |
| 04/21/2021 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
| 04/21/2021 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 04/21/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved |