Permit Number: T21CM02673
Parcel: 12406051A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM02673
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/31/2021 JVINCEN1 FIRE REVIEW Approved
04/06/2021 ROBERT SHERRY WATER REVIEW Completed
04/07/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Show the installation of the exhaust hood above the range/oven. If the hood is a recirculating unit, show how the minimum required exhaust will be provided for the kitchen. Reference: Section 403.3.2.3, IMC 2018.
2. Show how the dryer installation complies with Section 504.6, IMC 2018.
04/07/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide access to the shut-off valves for the stacked washers and dryers. Reference: Section 606.3, IPC 2018.
2. Show how 18-inches of clearance is provided for the cleanouts for the stacked washers and dryers. Reference: Section 708.1.9, IPC 2018.
04/12/2021 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/12/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/20/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
04/23/2021 LOREN MAKUS ENGINEERING REVIEW Passed
04/26/2021 STEVE SHIELDS ZONING REVIEW Approved