Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T21CM02671
Parcel: 12406051A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM02671
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/31/2021 JVINCEN1 FIRE REVIEW Approved
04/06/2021 ROBERT SHERRY WATER REVIEW Completed
04/07/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide access to the shut-off valves for the stacked washers and dryers. Reference: Section 606.3, IPC 2018.
2. Show how 18-inches of clearance is provided for the cleanouts for the stacked washers and dryers. Reference: Section 708.1.9, IPC 2018.
04/08/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Show the installation of the exhaust hood above the range/oven. If the hood is a recirculating unit, show how the minimum required exhaust will be provided for the kitchen. Reference: Section 403.3.2.3, IMC 2018.
2. Show how the dryer installation complies with Section 504.6, IMC 2018.
04/12/2021 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/12/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/20/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
04/23/2021 LOREN MAKUS ENGINEERING REVIEW Passed
04/26/2021 STEVE SHIELDS ZONING REVIEW Approved