Permit Number: T21CM02658
Parcel: 133323760

Address:
441 N BROWN AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM02658
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/22/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change Please verify the Service load center main breaker and backfeed breaker sizes will be in compliance with 2017 NEC.

Update the 3-line drawing with the breaker ratings.

Provide a manufacturer spec sheet for the solar modules.
07/02/2021 LSHAMIS1 ZONING REVIEW Reqs Change CDRC Transmittal
FROM: Loran Shamis, Planner

PROJECT: T21CM02658
Roof top solar panels (2nd review)
441 N Brown Av

TRANSMITTAL DATE: July 2, 2021

COMMENTS: Please resubmit drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

01. COMMENT: Zoning cannot approve the proposed plan until the previous zoning reviewer's comments are addressed. Please address the following comments:

02. COMMENT: After comparing the aerials to the plot plan, it has come to my attention that there is a possible non-permitted porch addition on the Northwest portion of the house. After doing research on PRO, there were no records for the porch addition that could be verified or found. If no permits are available relocate the solar panel away from the porch structure or a permit must be obtained for the porch addition.

03. COMMENT: Zoning will review the application on the next submittal.

If you have any questions about this transmittal, Contact Loran Shamis at Loran.Shamis@tucsonaz.gov.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans