Review Details: REVISION - - 1ST

Permit Number - T21CM02644
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/18/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

Verify that the existing meter can be used as a junction or splice box and is utilized according to the manufacturers listing instructions. NEC arts 110.3B, and 230.66.

Verify that the existing meter can if used as a splice box, meets size and cover requirements per NEC art 314.28A, B and C and art 314.41

Re f; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.