Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T21CM02644
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/18/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. Verify that the existing meter can be used as a junction or splice box and is utilized according to the manufacturers listing instructions. NEC arts 110.3B, and 230.66. Verify that the existing meter can if used as a splice box, meets size and cover requirements per NEC art 314.28A, B and C and art 314.41 Re f; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/18/2022 | VVERA1 | OUT TO CUSTOMER | Completed |