Permit Number: T21CM02622
Parcel: 12705077C

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T21CM02622
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/01/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical review comments and provide a written response.

Called Nicole to discuss electrical and left voice msg on 8-31-21 but no return call to the reviewer. The original approved electrical plan shows New Panel ‘K’ with a note stating “Future Loads”. This resubmittal for the revision does not have the note. Please clarify or provide an electrical floor plan showing all the equipment connections for review. Include a complete panel schedule along with load calculations.

Ref; 2018 IBC 107.2.1, 2017 NEC

Final Status

Task End Date Reviewer's Name Type of Review Description
09/01/2021 NGARCIA3 OUT TO CUSTOMER Completed