Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T21CM02622
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/01/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical review comments and provide a written response. Called Nicole to discuss electrical and left voice msg on 8-31-21 but no return call to the reviewer. The original approved electrical plan shows New Panel ‘K’ with a note stating “Future Loads”. This resubmittal for the revision does not have the note. Please clarify or provide an electrical floor plan showing all the equipment connections for review. Include a complete panel schedule along with load calculations. Ref; 2018 IBC 107.2.1, 2017 NEC |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/01/2021 | NGARCIA3 | OUT TO CUSTOMER | Completed |