Review Date Reviewer's Name Type of Review Description Status Comments
04/06/2021 STEVE SHIELDS ZONING REVIEW Approved
04/06/2021 SSHIELD1 ENGINEERING REVIEW Passed
04/06/2021 SSHIELD1 NPPO REVIEW Passed
04/21/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change PLAN REVIEW COMMENTS
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide two sets of updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
The City of Tucson adopted the 2018 IRC with amendments on 1/1/2019. Show the current code reference on the plans.
Consolidate pages of construction plans into a single .PDF file as prescribed at the PDSD web site. https://www.tucsonaz.gov/pdsd/online-permits
Sample plans are available at https://www.tucsonaz.gov/pdsd/residential-permits
SECTIONS - DETAILS:
1. Show connection at dwelling with fasteners (rafter on top plate with H2.5 or ledger with rafter hangers).
2. Show the Post Section Detail with #4 rebar in the footing, R403.1.
3. Notate and specify the size and length of anchor bolts, R403.1.
4. Show roof (uplift resistance) fasteners (H2.5) with appropriate uplift capacity, R802.11 amended.