Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T21CM02588
Parcel: 14029043A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM02588
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/05/2021 JVINCEN1 FIRE REVIEW Approved
04/05/2021 JGARCIA1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/07/2021 ROBERT SHERRY WATER REVIEW Completed
04/19/2021 STEVE SHIELDS ZONING REVIEW Approved
04/23/2021 LOREN MAKUS ENGINEERING REVIEW Passed
04/27/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM02588

GENERAL:
o Provide written responses to all review comments.
o Provide a complete plan set.
o Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
NA

BUILDING REVIEW COMMENTS:
Denied
1. The exit door located in the kitchen cannot be used as one of the required exits. Egress cannot travel through kitchens.
The door is currently labeled as an exit.
2. The swing of the door of the walk in cooler encroaches too far into a means of egress.
3. The double swing door adjacent to the exit, potentially encroaches too far into the door way of the exit.
4. Provide information on the tenant separation wall. Depending on the occupancy classification, the wall may require a fire
resistance rating per T508.4.
5. Provide a comprehensive egress plan that shows the separation of exit dimensions, travels distances, etc.
6. Show the accessible route in the building.
7. No door schedule provided. Provide a comprehensive door schedule.
Electrical Review
DENIED
1. If the kitchen exit door is going to be used as an exit and satisfy the other comments, additional exit lighting will be required in the kitchen area.
MECHANICAL REVIEW COMMENTS:
APPROVED
PLUMBING REVIEW COMMENTS:
APPROVED