Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM02586
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/28/2021 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 04/29/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Show how maintenance access will be provided for the external flow control device for the hydromechanical grease interceptor. Reference: Section 303.2, IPC 2018. 2. Interior waste piping upstream of the grease interceptor shall have a minimum slope of ¼” per foot (2% slope). Reference: Section 704.1, IPC 2018. 3. Provide the rim elevation of the next upstream sanitary manhole and the first-floor elevation. Determine the need for a backwater valve per Section 714.1, IPC 2018, as amended by the City of Tucson. 4. Provide separate indirect waste pipes for each compartment of the 3-compartment sink to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.1, IPC 2018. 5. Hand sinks in the kitchen are allowed to connect to the sanitary waste system instead of the grease waste system only if each sink has a sign posted above it stating, “HANDWASH SINK ONLY! NO FOOD PREPARATION OR DISHWASHING ALLOWED.” Reference: Section 1003.3, IPC 2018, as amended by the City of Tucson. |
| 04/29/2021 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 04/29/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. The mechanical plan shows high velocity diffusers for the make up air system in close proximity to the face of the Type I hoods. Verify that the location and type of make up air outlets complies with the hood manufacturer’s installation instructions and does not reduce the effectiveness of the exhaust system. Reference: Sections 304.1 and 508.1, IMC 2018. 2. The equipment submittals for the proposed Type I grease hood and supply air plenum show the equipment suspended from the overhead structure. Verify that the attachment method shown on detail 2/S1.0 complies with the manufacturer’s installation requirements. Reference: Section 304.1 and 507.2.4, IMC 2018. 3. Verify that the parapet height within ten feet of exhaust fan EF-1 is at least 42” above the walking surface of the roof or provide guards for the fan per Section 304.11, IMC 2018. 4. Verify that the evaporative cooling section of the makeup air unit is equipped with a recirculating water system. Reference: Section 928.2, IMC 2018 and ARS Title 45, Chapter 1, Article 12. See text at: (http://www.azleg.gov/viewdocument/?docName=http://www.azleg.gov/ars/45/00313.htm) |
| 05/10/2021 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 05/10/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 05/18/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 05/26/2021 | SBLOOD1 | ENGINEERING | REVIEW | Reqs Change | This project is within a mapped flood hazard area and requires a Floodplain Use Permit (FUP.) Please start a new FUP at our permit application web page: https://docs.tucsonaz.gov/Forms/tucsonpermitapp. Instructions: 1. Is this for a new or existing activity application? - Please select New Application. 2. Submission Type - Select Floodplain Use Permit. 3. Project Name - Enter a name for your project. 4. Select Street Name from the list. You can type the first two letters or number to get closer to your choice in the list. Then select the rest of the address in the boxes provided. 5. Type of Permit - Select Commercial or Residential (Residential is for work on single family residences and duplexes.) 6. Complete the Applicant Info. (Note APA# is for applicants with an advance payment account. Leave blank is you do not have an APA account. 7. Complete the Contractor, Owner and Architect/Engineer sections as applicable. 8. Supporting Documentation Upload - Provide a complete cost estimate for the project. You may also provide additional documents you think will be helpful. 9. Sign the application and submit. Stephen Blood (520) 837-4958 Stephen.blood@tucsonaz.gov |
| 05/27/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved |