Permit Number: T21CM02585
Parcel: 140270810

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T21CM02585
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/05/2021 JVINCEN1 FIRE REVIEW Approved
04/07/2021 ROBERT SHERRY WATER REVIEW Completed
04/20/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/20/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM02585
2705 E Valencia Rd
New Building

TRANSMITTAL: April 20, 2021
This site is located in the PI zone (UDC 4.7.28). Food Service is an allowed use in the zone subject to Use Specific Standard 4.9.13.Q, (Table 4.5-5)

1. Zoning has reviewed the building plans for compliance with DP21-0072 and although it appears that the building match the DP Zoning cannot approve the building plans until the DP is approved.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.
04/23/2021 LOREN MAKUS ENGINEERING REVIEW Reqs Change 1. DP21-0072 must be approved first.
04/27/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM02585

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Under Review

BUILDING REVIEW:
DENIED
1. A1: The location of the Class K extinguisher, indicated in the architectural notes, is not shown on the plans.
2. S1: The roof sheathing does not meet the minimum thickness requirements of T2304.8(1).
3. S2: Concrete slab a required to have a vapor retarder located between the slab and base course per 1907.1

ELECTRICAL REVIEW:
APPROVED

MECHANICAL REVIEW:
APPROVED

PLUMBING REVIEW:
APPROVED

Final Status

Task End Date Reviewer's Name Type of Review Description
04/28/2021 IMONSHI1 OUT TO CUSTOMER Completed