Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T21CM02584
Parcel: 120052500

Address:
4696 S 12TH AV

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T21CM02584
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/31/2021 JPEELDA1 FIRE REVIEW Approved
04/14/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. General: Please provide a floor plan indicating the tenant space, exits, restrooms, seating layout, plumbing fixtures, etc.
2. General: Please verify the requirements of the International Existing Building Code Sections 305.4.1 or 305.4.2 are met for partial or full building change of occupancy.
3. General: Please indicate on the drawing that an automatic sprinkler system is not required per the IBC Section 903.2.1.3, and therefore not required per the IEBC Section 1011.2.1.
4. General: Please indicate on the drawing no new construction will be included in the existing structure under this permit.
5. General: Please provide written responses to all review comments.
04/20/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/20/2021 SSHIELD1 ENGINEERING REVIEW Passed
04/20/2021 STEVE SHIELDS ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/21/2021 IMONSHI1 OUT TO CUSTOMER Completed