Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM02581
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/06/2021 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 04/06/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 04/06/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 04/06/2021 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 04/06/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A-1; Key Plan: Per the IBC Section 1011.10, a spiral stair is allowed to be used as a component in a means of egress from a space not more than 250 SF in area and serving not more than 5 occupants. Please verify on the drawings those requirements are met. 2. General: Is this stairway the only exit from the upper floor? Please verify. 3. General: The new spiral stair shall be a deferred submittal that meets the requirements of the IBC Section 107.3.4.1. Please indicate that statement on the drawings. 4. General: Please provide written responses to all review comments. |
| 04/13/2021 | JPEELDA1 | FIRE | REVIEW | Reqs Change | 1. Sheet A-1; Key Plan: Per the IBC Section 1011.10, a spiral stair is allowed to be used as a component in a means of egress from a space not more than 250 SF in area and serving not more than 5 occupants. Please verify on the drawings those requirements are met. 2. General: Is this stairway the only exit from the upper floor? Please verify. 3. General: The new spiral stair shall be a deferred submittal that meets the requirements of the IBC Section 107.3.4.1. Please indicate that statement on the drawings. 4. General: Please provide written responses to all review comments. |
| 04/15/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Passed | |
| 04/21/2021 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
| 04/21/2021 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | ZONING REVIEW TRANSMITTAL FROM: PDSD Zoning Review PROJECT: T21CM02581 340 N Main Ave Demo existing staircase and add spiral staircase and exterior gates. TRANSMITTAL: April 21, 2021 COMMENTS: the following comments are relative to an application for Historic Review (UDC 5.8.8). This site is located in the HO-3 zone (UDC 4.7.15). Exterior work requires Historic review. This review must be completed and approved prior to approval of this plan. |
| 04/21/2021 | STEVE SHIELDS | ZONING_HISTORIC | REVIEW | Needs Review |