Permit Number: T21CM02580
Parcel: 136082280

Address:
9501 E 33RD ST

Review Status: Completed

Review Details: OTHER

Permit Number - T21CM02580
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/07/2021 JGARCIA1 BUILDING-RESIDENTIAL REVIEW Passed
04/26/2021 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: T21CM02580
9501 E 33rd St
Storage Container (1st Review)

TRANSMITTAL DATE: April 26, 2021

This site is located in the R-1 zone (UDC 4.7.8). A single-family residence is a permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.B.5-.9.

1. Based on current aerial photos there are several other structures on site that are not shown on this plot plan. Show all structures and include them in the lot coverage calculation.

2. The lot coverage provided is not correct and should include all any space on site used for parking vehicles. See residential plot plan requirements found at: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf.

3. Per UDC Table 6.3-2.A: DIMENSIONAL STANDARDS FOR THE R-1, R-2, R-3, MH-1, & MH-2 Zones, R-1 zone, Residential Use to Residential Zone the required perimeter yard setbacks to the north and west property line is 6’-0” or 2/3 the height of the building exterior wall. Perimeter yard setbacks are based on a measurement from design grade to the highest point of the wall, see UDC Article 6.4.5 & figure 6.4.5-A. As most storage containers are 8’-0” the required perimeter yard setback is 6’-0”, proposed is 4’ to the east property line. At a minimum a neighbor signoff for reduced perimeter yard setback is required. The following text shall be added to the plot plan and signed by the adjacent owners:

My Name is __________________ and I am the owner of the property located at ________________________. I have reviewed the site plan and I have no objection to structure being located or constructed ______ feet from the property line as depicted on the site plan.

Signature: _____________________________

Date: _________________________________

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/27/2021 PCAMARE1 OUT TO CUSTOMER Completed