Permit Number: T21CM02503
Parcel: 11712017A

Address:
55 N 6TH AV

Review Status: Completed

Review Details: OTHER

Permit Number - T21CM02503
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/19/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.

Indicate conductor sizes, quantities and types for all the new feeders. Not in the panel schedules or line diagram.

Verify that there is a mechanical equipment maintenance receptacle on the roof as required per NEC art 210.

Please update the plans and re-submit.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, City of Tucson Commercial Permit/Plan Submittal Requirements.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/20/2021 IMONSHI1 OUT TO CUSTOMER Completed