Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T21CM02481
Parcel: 12218236B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM02481
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/31/2021 JPEELDA1 FIRE REVIEW Approved
04/05/2021 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/05/2021 ROBERT SHERRY WATER REVIEW Completed
04/05/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide a metering faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
2. Provide tempered water for the lavatories and public hand-washing sinks in restrooms using approved devices conforming to ASSE 1070. Reference: Sections 419.5 and 607.1.2, IPC 2018.
3. Clarify the specifications for the water fountain. The drawing shows a single-level drinking fountain and the fixture schedule shows model numbers for both single-level and dual-level drinking fountains. Provide the number of drinking fountains that complies with the requirements of Sections 2902.1 and 2902.5, IBC 2018 and Section 410.3, IPC 2018.
4. Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018.
5. Keynote #10 on sheet P-1 shows water being supplied for a coffee counter. At a minimum, coffee machines connected directly to water service require the use of a backflow preventer listed to either ASSE 1022, ASSE 1024, or an air gap. Reference: Section 608.17.1.2, IPC 2018.
04/05/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/07/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Revise detail 10/M-3 to show the condensate drain for the rooftop unit terminating at an approved disposal location. Reference: Section 307.2.1, IMC 2018, as amended by the City of Tucson.
04/14/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.

Provide plans and evidence on the plans that the proposed exterior lighting fully complies with the Outdoor Lighting Code. See section 104 for plan submittal requirements.

Provide lighting plans with the following information on the plans;

(a) Provide a complete luminaire schedule for each parcel, if more that one, include for each separate parcel. Include shielding and lamp color output temperature.

(b) Size of the parcel in acres. It appears there are several parcels. If true, then provide total lumen calculations and all other required information for each parcel, per section 104.2.1.

(c)See table 401.1, lighting area and option and indicate this information in the lighting site plan for each parcel, also show the locations and types of all exterior luminaires including existing.

(d) Section 402.1 (light source color temperature requirements 3500K), shielding requirements, etc .

(e) Provide a complete inventory (quantities) for each type of luminaire on the parcel.

(f) Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2.

(g) Specify any exceptions used.

(h) Curfew lighting controls If applicable.

Do not confuse the Outdoor Lighting Code with the IECC.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2012 Tucson/Pima County Outdoor Lighting Code,

City of Tucson Commercial Plan Submittal Requirements
04/21/2021 SSHIELD1 ENGINEERING REVIEW Passed
04/21/2021 STEVE SHIELDS ZONING REVIEW Approved