Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T21CM02473
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/15/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. Indicate conductor sizes, quantities and types for the secondary feeders to the new electrical service from the Utility Transformer. Please account for panels ‘A’ and ‘B’ in the load calculations. Please update the plans and re-submit. Ref; 2018 IBC sec 107.2.1, 2017 NEC, City of Tucson Commercial Permit/Plan Submittal Requirements. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/16/2021 | IMONSHI1 | OUT TO CUSTOMER | Completed |