Permit Number: T21CM02468
Parcel: 123130320

Address:
924 E EDISON ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T21CM02468
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/22/2021 SBLOOD1 ENGINEERING REVIEW Passed
04/26/2021 PIMA COUNTY BUILDING-RESIDENTIAL REVIEW Approved
06/01/2021 PAUL CAMARENA ZONING REVIEW Reqs Change FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: T21CM02468
Roof top Solar Panels (1st Review)
924 E Edison ST

TRANSMITTAL DATE: June 1, 2021



COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


o COMMENT: Zoning has reviewed the plan and cannot approve at this time. Please address the following comments.

o COMMENT: After comparing the aerials to the plot plan it has come to my attention that there is a possible non-permitted porch addition on the South portion of the house. After doing research on PRO there were no records for the porch addition that could be verified or found. If no permits are available relocate the solar panel away from the porch structure or a permit must be obtained for the porch addition.


o This site is located in the NR-1 zone (UDC 5.10.3
o Prior to zoning approval an NPZ review and approval is required. Owner is proposing to add a PV system in porch to the rear of the existing dwelling. The property fronts on Edison.


o COMMENT: Zoning will review the application on the next submittal




If you have any questions about this transmittal, Contact Paul Camarena any time during the week by email Paul.Camarena@Tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans