Review Date Reviewer's Name Type of Review Description Status Comments
03/25/2021 JPEELDA1 FIRE REVIEW Reqs Change The building is VB construction and 3,813 sq ft that means you will need to meet 1,750 gpm at the closest hydrant. Please provide a letter from Tucson Water stating that can be met and provide information to TFD.
The farthest part of the building shall be no further than 400' as the hose lays from the nearest hydrant or fire sprinklers shall be installed. Please include the distance in your plan set and or to TFD
Jennifer.Peel-Davis@TucsonAz.gov
520-837-7033
04/01/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change An approved development plan is not to be used for construction of on-site utilities (e.g. water service to the building, building sewer, etc.). Provide the civil plans showing the installation of the water service to the building and the installation of the building sewer as part of the building plan set. Reference: Sections 107.2.1 and 107.2.6, IBC 2018.
04/01/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
04/01/2021 ROBERT SHERRY WATER REVIEW Completed
04/01/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet TS.1; General Notes (Applicable Codes): The IBC, IFC, IFGC, IMC, IPC, and IECC should be revised to the 2018 Editions. The 2012 IRC should be removed. The NEC should be revised to the 2017 Edition.
2. Sheet TS.1; 'R' and 'U' Values: Please revise the reference to the 2018 IECC.
3. Sheet A.1; Partition Types: For the 2 hour fire resistant rated wall 8B, please provide a U.L. Listing Number for the wall construction.
4. Sheet S.1; General Structural Notes: Please update all code references to the 2018 IBC and revise as required.
5. General: All drawings should be restamped with a seal that is not expired.
6. General: Please provide structural calculations.
7. General: Please provide a Special Inspections Certificate with Parts A and B completed.
8. General: Please provide written responses to all review comments.
04/12/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.

The NEC code reference is outdated. The currently adopted NEC is 2017.

The electrical plans are sealed by an EE that no longer exists.

Please update the plans and re-submit.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, City of Tucson Commercial Permit/Plan Submittal Requirements.
04/16/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM02425
3520 S 6th Ave
New Shell Building

TRANSMITTAL: April 16, 2021
This site is located in the C-2 zone (UDC 4.7.21).

1. Associated DP15-0200 has exceeded the allowed 3 years to obtain a building permit, see UDC Article 3.3.3.G.6.a.(1).

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov
04/16/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
04/16/2021 LOREN MAKUS ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/19/2021 PCAMARE1 OUT TO CUSTOMER Completed