Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM02414
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/18/2021 | JVINCEN1 | FIRE | REVIEW | Approved | |
| 04/01/2021 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 04/01/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A2.01; Building Section 7: Please provide structural calculations for the new masonry wall and new foundation at the drive through window enclosure, and indicate on the drawings. 2. Sheet A2.01; Building Section 7: Please provide structural calculations for the new lintel over the new opening through the existing wall. 3. Sheet A2.01; Building Section 7: Please provide structural calculations for the new lintel over the new drive through window enclosure opening, and indicate on the drawings. 4. General: A Special Inspections Certificate was included in this submittal. Please complete Parts A and B of that Certificate. 5. General: Please provide written responses to all review comments. |
| 04/05/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. 2. Demonstrate energy code compliance for the addition to the building envelope using calculations based on the current code (e.g. COMcheck, additions). Reference: Section C502.1, International Energy Conservation Code 2018. 3. Building section 7/A2.01 shows a wall opening for new mechanical work. Show the proposed mechanical work and how it relates to the existing mechanical system. Reference: Section 107.2.1, IBC 2018. 4. Provide calculations to verify that adequate ventilation will be provided for the new occupied space. Reference: Section 403.3.1.1, IMC 2018. |
| 04/05/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. 2. Provide plumbing plans for the new work, including water isometrics and waste and vent isometrics. Show how the new work will be connected to the existing plumbing systems. Reference: Section 107.2.1, IBC 2018. 3. The addition does not have a means of secondary roof drainage. Provide structural calculations to show that the canopy can safely support the maximum possible water depth caused by ponding if the primary roof drains are assumed to be blocked or provide secondary roof drainage. Reference: Section 1101.7, IPC 2018. |
| 04/05/2021 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 04/12/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following Electrical Plan Review comments. Provide a written response. . Designing the site Electrical constitutes the practice of engineering. Provide plans sealed by an Arizona Registrant. Reference Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304 Ref; 2018 IBC sec 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. Tucson/Pima County Outdoor Lighting Code |
| 04/12/2021 | DSANTAC2 | ENGINEERING | REVIEW | Reqs Change | Please address the following Electrical Plan Review comments. Provide a written response. . Designing the site Electrical constitutes the practice of engineering. Provide plans sealed by an Arizona Registrant. Reference Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304 Ref; 2018 IBC sec 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. Tucson/Pima County Outdoor Lighting Code |
| 04/19/2021 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | ZONING REVIEW TRANSMITTAL FROM: PDSD Zoning Review PROJECT: T21CM02414 6610 E Grant Rd Drive-Through Addition TRANSMITTAL: April 19, 2021 This site is located in the C-2 zone (UDC 4.7.21). Food Service is a permitted use in this zone (Table 4.8-4) subject to Use Specific Standards 4.9.4.M.1 and 4.9.13.P. 1. Zoning has reviewed the building plans but cannot approve until a development package (DP), commercial site plan, has been submitted and approved. This DP shall meet the requirements found in the Checklist for Minor Development Changes to Existing Commercial/Industrial Site: https://www.tucsonaz.gov/files/pdsd/forms/Minor_Changes_to_Commercial_Industrial_Sites_.pdf. This DP is a separate submittal and shall be submitted at: https://docs.tucsonaz.gov/Forms/tucsonpermitapp. If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov. |