01/03/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

1. Per the revision letter submitted, the existing 3 phase electrical service located at Building #1 is to be changed to a single-phase service and also feeds panel ‘P2’via panel ‘P1’ . Ref; Plan sheet E300.1. The panel schedule for panel ‘P1’ shows a 400 amp rated panel with a 100 amp MCB. This is undersized for the calculated load. Please revise the panel schedule showing the correct MCB rating.

2. Why does the line diagram not include panel ‘P2’ ?

3. How is panel ‘P3’ and its loads affected by the conversion to single phase?

4. Is the electrical power and lighting in building #1 existing? If yes, please indicate this on the power floor plan.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, 2012 Tucson/Pima County outdoor Lighting Code.