Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T21CM02308
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/06/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Previous Comment 4; Accessible Entrances: The 2018 International Existing Building Code Section 305.7 indicates the route to the primary function area of a building shall be accessible. In this building, the primary function area is the reception area. The ramp on the south side of Building 1 leads to a door at an open treatment room, which would not fall under a primary function area.. An appeal to the Building Official may be made to approve the ramp entering the building at the treatment room, or the interior room arrangement may be revised so the ramp entrance would be at the primary building function room. 2. General: Please provide an enlarged, dimensioned floor plan for the restroom and indicate the grab bars per the ICC/ANSI A117.1 Figures 604.5.1 and 604.5.2. 3. General: Please provide written responses to all review comments. |
| 07/08/2021 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 07/08/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Comment not addressed. [Initial comment: Changing from a massage use to a beauty salon use requires additional ventilation, including required exhaust. Reference: Section 403.3.1, IMC 2018.] 2. Provide locking access port caps for the condensing units per Section 1101.10, IMC 2018 or locate the condensing unit in a controlled space. |