Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM02308
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/18/2021 | JVINCEN1 | FIRE | REVIEW | Approved | |
03/31/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A100; Code Review: Building 1 indicates an additional 55 SF to the 1933 SF of the building. Is this additional SF for the covered patio? Please verify. 2. Sheet A100; Code Review: Building 2 indicates an additional 49 SF to the 493 SF of the building. Is this additional SF for the covered patio? Please verify. 3. Sheet A100; Code Review: The Code Review indicates 'No change in building height' and 'No change in building area'. In addition, 'No change in use' is indicated. Does the current tenant have an existing Certificate of Occupancy? What is the purpose of this permit? 4. Sheet A101; Floor Plans: Building 1 and 2 appear to have no accessible entrances to the buildings. At least one accessible entrance is required per the IBC Section1105 and the IEBC Section 305.4.2. Please verify. 5. General: Do Buildings 1, 2, and 3 have the same address? Typically, separate buildings require separate Certificates of Occupancy. Please verify. 6. General: Please verify on the drawings there is no new work required for this project in any of the three buildings. 7. General: This appears to be a change of use from the previous tenant. The most recent Certificate of Occupancy indicated a restaurant use. Please verify. 8. General: Please indicate on the drawings the Construction Type and the Automatic Sprinkler information. 9. General: Please provide written responses to all review comments. |
04/01/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Changing from a massage use to a beauty salon use requires additional ventilation, including required exhaust. Reference: Section 403.3.1, IMC 2018. |
04/01/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
04/01/2021 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Beauty salons require a reduced pressure backflow assembly after the water meter. This address doesn’t appear to have one. |
04/08/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Passed | |
04/12/2021 | SBLOOD1 | ENGINEERING | REVIEW | Passed | |
04/16/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
04/16/2021 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |