Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T21CM02279
Parcel: Unknown

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM02279
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/27/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.

As per the previous electrical plan review comments, a written response and additional information was requested..Could not locate either in the resubmittal. Please revise the plans and re-submit with the following information requested per the previous review.

Previous review comments;

Provide more detail for the installation of the traffic power pedestals, such as:

(a) Complete line diagram including, Voltage and Phase, Grounding, Available Fault Current and AIC and amp rating of the electrical equipment. Conduit and conductor sizes, quantities and types for any feeders such as secondary conductors.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, City of Tucson Commercial Permit/Plan Submittal Requirements.