Review Date Reviewer's Name Type of Review Description Status Comments
04/13/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.



Provide more detail for the installation of the traffic power pedestals, such as:



(a) Complete line diagram including, Voltage and Phase, Grounding, Available Fault Current and AIC and amp rating of the electrical equipment. Conduit and conductor sizes, quantities and types for any feeders such as secondary conductors.



Ref; 2018 IBC sec 107.2.1, 2017 NEC, City of Tucson Commercial Permit/Plan Submittal Requirements.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/14/2021 PCAMARE1 OUT TO CUSTOMER Completed