Permit Number - T21CM02278
Review Name: OTHER
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/13/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. Provide more detail for the installation of the traffic power pedestals, such as: (a) Complete line diagram including, Voltage and Phase, Grounding, Available Fault Current and AIC and amp rating of the electrical equipment. Conduit and conductor sizes, quantities and types for any feeders such as secondary conductors. Ref; 2018 IBC sec 107.2.1, 2017 NEC, City of Tucson Commercial Permit/Plan Submittal Requirements. |