Permit Number: T21CM02256
Parcel: Unknown

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM02256
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/16/2021 JPEELDA1 FIRE REVIEW Approved
03/30/2021 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/30/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
03/31/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Revise the COMcheck envelope assembly description for the roof insulation to correspond to the building section. The building section shows cavity insulation for the roof, not continuous insulation.
2. Secure the refrigerant circuit access ports of the condensing units to prevent unauthorized access. Reference: Section 1101.10, IMC 2018
03/31/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide secondary roof drainage. The 4” diameter overflow opening in the collector box will not serve as a secondary roof drain if the primary roof drain (the scupper) is blocked. Reference: Sections 1108.1, 1108.2 and 1108.3, IPC 2018.
03/31/2021 ROBERT SHERRY WATER REVIEW Completed
04/08/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.

Provide plans and evidence on the plans that the proposed exterior lighting fully complies with the Outdoor Lighting Code. See section 104 for plan submittal requirements.

Provide lighting plans with the following information on the plans;

(a) Provide a complete luminaire schedule for each parcel, if more that one, include for each separate parcel. Include shielding and lamp color output temperature.

(b) Size of the parcel in acres. It appears there are several parcels. If true, then provide total lumen calculations and all other required information for each parcel, per section 104.2.1.

(c)See table 401.1, lighting area and option and indicate this information in the lighting site plan for each parcel, also show the locations and types of all exterior luminaires including existing.

(d) Section 402.1 (light source color temperature requirements 3500K), shielding requirements, etc .

(e) Provide a complete inventory (quantities) for each type of luminaire on the parcel.

(f) Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2.

(g) Specify any exceptions used.

(h) Curfew lighting controls If applicable.

Do not confuse the Outdoor Lighting Code with the IECC.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2012 Tucson/Pima County Outdoor Lighting Code,

City of Tucson Commercial Plan Submittal Requirements
04/12/2021 LOREN MAKUS ENGINEERING REVIEW Reqs Change The development package must be approved first.
04/13/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM02256, T21CM02284 T21CM02285
7821 E Wrightstown Road
Construction Services

TRANSMITTAL: April 13, 2021
This site is located in the C-2 zone (UDC 4.7.21). Food Service is a permitted use in this zone (Table 4.8-4) subject to Use Specific Standard 4.9.13.P.

1. Zoning has reviewed the building plans for compliance with DP21-0062 and although the building plans appear to match the DP until the DP is approved Zoning cannot approve the building plans.

If you have any questions about this transmittal, please contact Steve Shields at Steve.Shields@tucsonaz.gov. My email will return an automatic response stating that I have retired but I am currently working as a contract employee and will respond to your questions via email regarding this review.