Permit Number: T21CM02179
Parcel: 12110005D

Address:
4730 E GRANT RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM02179
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/27/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
04/28/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Revise the domestic water isometric, A/P006, to show how the recirculating hot water loop (i.e. the hot water source) will be located within the maximum distance for the hot water branch piping for public lavatory faucets noted in Table C404.5.1, IECC 2018. [Initial comment: Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018.]
2. If the water heater is to be mounted on a stand on the floor slab, revise detail D/P003 to reflect that condition. Reference: Section 107.2.1, IBC 2018. [Initial comment: Provide structural calculations for the mounting shelf for the water heater to show that the water heater will be safely supported from the building structure. Reference: Section 301.2, IPC 2018.]
05/06/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved