Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T21CM02179
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/27/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 04/28/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Revise the domestic water isometric, A/P006, to show how the recirculating hot water loop (i.e. the hot water source) will be located within the maximum distance for the hot water branch piping for public lavatory faucets noted in Table C404.5.1, IECC 2018. [Initial comment: Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018.] 2. If the water heater is to be mounted on a stand on the floor slab, revise detail D/P003 to reflect that condition. Reference: Section 107.2.1, IBC 2018. [Initial comment: Provide structural calculations for the mounting shelf for the water heater to show that the water heater will be safely supported from the building structure. Reference: Section 301.2, IPC 2018.] |
| 05/06/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved |