Permit Number: T21CM02170
Parcel: 11504490A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM02170
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/14/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Coordinate details 2/A-2 and 101/M-2: the architectural detail calls for ½-inch threaded rods to suspend the fan coil units while the mechanical detail only calls for 3/8-inch threaded rods. [Initial comment: Provide structural calculations and details to show how the fan coil units are to be connected to the building structure. Reference: Section 302.1, IMC 2018.]
04/14/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
04/26/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved