Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T21CM02170
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/14/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Coordinate details 2/A-2 and 101/M-2: the architectural detail calls for ½-inch threaded rods to suspend the fan coil units while the mechanical detail only calls for 3/8-inch threaded rods. [Initial comment: Provide structural calculations and details to show how the fan coil units are to be connected to the building structure. Reference: Section 302.1, IMC 2018.] |
04/14/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
04/26/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |