Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T21CM02170
Parcel: 11504490A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM02170
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/11/2021 DTRAMME1 ENGINEERING REVIEW Passed
03/15/2021 JPEELDA1 FIRE REVIEW Approved
03/25/2021 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/25/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
03/30/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide structural calculations and details to show how the fan coil units are to be connected to the building structure. Reference: Section 302.1, IMC 2018.
03/30/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Indirect waste receptors (e.g. P-7) shall not be installed in concealed spaces. Provide ready access to the waste receptor. Reference: Section 802.4, IPC 2018.
03/30/2021 ROBERT SHERRY WATER REVIEW Completed
04/05/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.

Verify compliance for the 75 KVA transformer mounted above the bathroom ceiling. NEC 450.13(B).

Ref; 2018 IBC sec 107.2.1, 2017 NEC, City of Tucson Commercial Permit/Plan Submittal Requirements.
04/09/2021 STEVE SHIELDS ZONING REVIEW Approved