Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM02170
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/11/2021 | DTRAMME1 | ENGINEERING | REVIEW | Passed | |
03/15/2021 | JPEELDA1 | FIRE | REVIEW | Approved | |
03/25/2021 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
03/25/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
03/30/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide structural calculations and details to show how the fan coil units are to be connected to the building structure. Reference: Section 302.1, IMC 2018. |
03/30/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Indirect waste receptors (e.g. P-7) shall not be installed in concealed spaces. Provide ready access to the waste receptor. Reference: Section 802.4, IPC 2018. |
03/30/2021 | ROBERT SHERRY | WATER | REVIEW | Completed | |
04/05/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. Verify compliance for the 75 KVA transformer mounted above the bathroom ceiling. NEC 450.13(B). Ref; 2018 IBC sec 107.2.1, 2017 NEC, City of Tucson Commercial Permit/Plan Submittal Requirements. |
04/09/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved |