Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T21CM02161
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/28/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Comment not resolved, provide a detail showing how the hood is to be supported from the building structure. Note: Sheet A2.0 is for a building located in Mesa, Arizona. [Initial comment: Provide structural calculations and details to show that the Type I hood is supported from the building structure in accordance with Section 507.2.4, IMC 2018 (the hood hanging weight plus the weight of personnel working in or on the hood). Reference: Section 302.1, IMC 2018.] 2. Comment not resolved, the wiring diagram on sheet M5.0 does not include provisions for water recirculation. If evaporative cooling is desired, provide a make-up air system equipped with a recirculating water system [Initial comment: Verify that the evaporative cooling section of the make-up air unit is equipped with a recirculating water system. Reference: Section 928.2, IMC 2018 and ARS Title 45, Chapter 1, Article 12. See text at: (http://www.azleg.gov/viewdocument/?docName=http://www.azleg.gov/ars/45/00313.htm).] |
06/28/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed |