Permit Number: T21CM02161
Parcel: 132082380

Address:
1999 E AJO WY

Review Status: Completed

Review Details: OTHER

Permit Number - T21CM02161
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/01/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide structural calculations and details to show that the Type I hood is supported from the building structure in accordance with Section 507.2.4, IMC 2018 (the hood hanging weight plus the weight of personnel working in or on the hood). Reference: Section 302.1, IMC 2018.
2. Show that the hood installation complies with Section 507.2.6, IMC 2018 with regard to a smooth, cleanable, non-absorbent, and non-combustible material installed between the hood and the wall and extending 18” beyond the hood.
3. Verify that the evaporative cooling section of the makeup air unit is equipped with a recirculating water system. Reference: Section 928.2, IMC 2018 and ARS Title 45, Chapter 1, Article 12. See text at: (http://www.azleg.gov/viewdocument/?docName=http://www.azleg.gov/ars/45/00313.htm).
04/01/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Revise the natural gas system to provide an automatic fuel shutoff valve interlocked with the hood fire suppression system. Reference: Section 904.3.3, IFC 2018.
04/08/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/09/2021 IMONSHI1 OUT TO CUSTOMER Completed